MINI MCR-SL-U-UI-SP-NC 数据手册
https://www.phoenixcontact.com/gb/products/2810078
Signal conditioner - MINI MCR-SL-U-UI-SP-NC - 2810078
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
MCR 3-way signal conditioner, with configurable input/output, for electrical isolation and conversion of analog
signals up to 30 V, with spring-cage connection, standard configuration. Replacement part: 2902040 MINI
MCR-2-UI-UI-PT.
Your advantages
Power supply possible via the foot element (TBUS)
Low power consumption
Up to 12 signal combinations can be configured using DIP switches
3-way isolation
Highly-compact isolating amplifier for electrical isolation, conversion, amplification, and filtering of 24 V or
30 V DC signals to create standard analog signals
Key Commercial Data
Packing unit
1 pc
GTIN
GTIN
4046356043588
Weight per Piece (excluding packing)
79.600 g
Custom tariff number
85437090
Country of origin
Germany
Note
Made to Order (non-returnable)
Technical data
Dimensions
Width
6.2 mm
Height
93.1 mm
Depth
102.5 mm
Ambient conditions
Ambient temperature (operation)
-20 °C ... 65 °C
01/02/2020 Page 1 / 8
https://www.phoenixcontact.com/gb/products/2810078
Signal conditioner - MINI MCR-SL-U-UI-SP-NC - 2810078
Technical data
Ambient conditions
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Degree of protection
IP20
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Input data
Number of inputs
1
Configurable/programmable
Yes, unconfigured
Voltage input signal
0 V ... 24 V
0 V ... 30 V
max. input voltage
50 V DC
Input resistance of voltage input
approx. 125 kΩ (0 ... 24 V)
approx. 155 kΩ (0 ... 30 V)
Output data
Number of outputs
1
Configurable/programmable
Yes, unconfigured
Voltage output signal
0 V ... 10 V
0 V ... 5 V
1 V ... 5 V
2 V ... 10 V
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Max. output voltage
≤ 12.5 V
Max. output current
28 mA
Short-circuit current
≤ 22 mA
Load/output load voltage output
> 10 kΩ
Load/output load current output
< 500 Ω (at 20 mA)
Ripple
< 20 mVPP (at 500 Ω)
< 20 mVPP (at 10 kΩ)
Power supply
Nominal supply voltage
24 V DC
Supply voltage range
19.2 V DC ... 30 V DC (The DIN rail bus connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used to bridge the
supply voltage. It can be snapped onto a 35 mm DIN rail according to
EN 60715))
Max. current consumption
< 19 mA (at 24 V DC incl. load)
Power consumption
< 450 mW
Connection data
Connection method
Spring-cage connection
Stripping length
8 mm
Conductor cross section solid
0.2 mm² ... 2.5 mm²
01/02/2020 Page 2 / 8
https://www.phoenixcontact.com/gb/products/2810078
Signal conditioner - MINI MCR-SL-U-UI-SP-NC - 2810078
Technical data
Connection data
Conductor cross section flexible
0.2 mm² ... 2.5 mm²
Conductor cross section AWG
24 ... 12
General
No. of channels
1
Maximum transmission error
< 0.1 % (of final value)
< 0.4 % (Without adjustment)
Maximum temperature coefficient
< 0.01 %/K
Temperature coefficient, typical
< 0.002 %/K
Limit frequency (3 dB)
approx. 100 Hz
Step response (10-90%)
approx. 3.5 ms
Protective circuit
Transient protection
Electrical isolation
Basic insulation according to EN 61010
Overvoltage category
II
Degree of pollution
2
Rated insulation voltage
50 V AC/DC
Test voltage, input/output/supply
1.5 kV (50 Hz, 1 min.)
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color
green
Housing material
PBT
Mounting position
any
Assembly instructions
To bridge the supply voltage, the DIN rail connector (ME 6,2 TBUS-2
1,5/5-ST-3,81 GN, Order No. 2869728) can be used. It can be snapped
onto a 35 mm DIN rail according to EN 60715.
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
EMC data
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
Typical deviation from the measuring range final value
5%
Designation
Fast transients (burst)
Standards/regulations
EN 61000-4-4
Typical deviation from the measuring range final value
5%
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Typical deviation from the measuring range final value
5%
Standards and Regulations
01/02/2020 Page 3 / 8
https://www.phoenixcontact.com/gb/products/2810078
Signal conditioner - MINI MCR-SL-U-UI-SP-NC - 2810078
Technical data
Standards and Regulations
Electromagnetic compatibility
Conformance with EMC directive
Noise emission
EN 61000-6-4
Connection in acc. with standard
CUL
Standards/regulations
EN 61000-4-2
Designation
Electromagnetic RF field
Standards/regulations
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
Designation
Conducted interferences
Standards/regulations
EN 61000-4-6
Electrical isolation
Basic insulation according to EN 61010
Fire protection for rail vehicles (DIN EN 45545-2) R22
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23
HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24
HL 1 - HL 2
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Application drawing
Signal conversion to uninterruptible power supply (UPS)
01/02/2020 Page 4 / 8
https://www.phoenixcontact.com/gb/products/2810078
Signal conditioner - MINI MCR-SL-U-UI-SP-NC - 2810078
Block diagram
01/02/2020 Page 5 / 8
https://www.phoenixcontact.com/gb/products/2810078
Signal conditioner - MINI MCR-SL-U-UI-SP-NC - 2810078
Dimensional drawing
Classifications
eCl@ss
eCl@ss 4.0
27210100
eCl@ss 4.1
27210100
eCl@ss 5.0
27210100
eCl@ss 5.1
27210100
eCl@ss 6.0
27210100
eCl@ss 7.0
27210120
eCl@ss 8.0
27210120
eCl@ss 9.0
27210120
ETIM
ETIM 4.0
EC002653
ETIM 5.0
EC002653
ETIM 6.0
EC002653
ETIM 7.0
EC002653
01/02/2020 Page 6 / 8
https://www.phoenixcontact.com/gb/products/2810078
Signal conditioner - MINI MCR-SL-U-UI-SP-NC - 2810078
Classifications
UNSPSC
UNSPSC 6.01
30211506
UNSPSC 7.0901
39121008
UNSPSC 11
39121008
UNSPSC 12.01
39121008
UNSPSC 13.2
39121008
UNSPSC 19.0
39121008
Accessories
Accessories
DIN rail connector
DIN rail bus connectors - ME 6,2 TBUS-2 1,5/5-ST-3,81 GN - 2869728
DIN rail connector for DIN rail mounting. Universal for TBUS housing. Gold-plated contacts, 5-pos.
Marking material
Marking label - MINI MCR-DKL-LABEL - 2810272
Label for extended marking of MINI MCR modules in connection with the MINI MCR-DKL
Transparent cover - MINI MCR DKL - 2308111
Fold up transparent cover for MINI MCR modules with additional labeling option using insert strips and flat Zack
marker strip 6.2 mm
Power module
01/02/2020 Page 7 / 8
https://www.phoenixcontact.com/gb/products/2810078
Signal conditioner - MINI MCR-SL-U-UI-SP-NC - 2810078
Accessories
Power terminal block - MINI MCR-SL-PTB - 2864134
MCR power terminal block for supplying several MINI Analog modules via the DIN rail connector, with screw
connection, maximum current consumption of up to 2 A
Power terminal block - MINI MCR-SL-PTB-SP - 2864147
MCR feed-in terminal for supplying several MINI Analog modules via a DIN rail connector, with spring-cage
connection, maximum current consumption of up to 2 A. Replacement part: 2902067 MINI MCR-2-PTB-PT.
Power supply
Power supply unit - MINI-SYS-PS-100-240AC/24DC/1.5 - 2866983
Primary-switched MINI POWER supply for DIN rail mounting, input: 1-phase, output: 24 V DC/1.5 A
Power supply unit - MINI-PS-100-240AC/24DC/1.5/EX - 2866653
Primary-switched power supply MINI POWER for DIN rail mounting, input: 1-phase, output: 24 V DC/1,5 A, for the
potentially explosive area
Phoenix Contact 2020 © - all rights reserved
http://www.phoenixcontact.com
01/02/2020 Page 8 / 8
MINI MCR-SL-U-UI-SP-NC 价格&库存